The type designation of a DIINNO meter tells you everything essential: design, connection to the smart meter gateway, energy direction, tariff, interface and accuracy class. It is based on the type codes in the type examination certificates and our data sheets. The meters are manufactured by Holley Technology and distributed in Germany by DIINNO.
The structure in one line
Series – (i) Direction Tariff Interface Class/option
First the series (plug-in or screw-mounted, three-phase or single-phase), then the letters from left to right. Not every series uses every position – the tables below show which.
Series: plug-in or screw-mounted?
| Series | Design | Network | Current |
|---|---|---|---|
| EHZ541 / EHZ541-i | eHZ, plug-in design to DIN 43857-2 – plugged onto the meter board with contact device (BKE) | three-phase (also usable single-phase) | 0.25–5 (60) A |
| DTZ541 | three-point mounting to DIN 43857-2 – screwed on | three-phase | 0.25–5 (60) A or 0.25–5 (100) A |
| DDZ285 | three-point mounting to DIN 43857-2 | single-phase | 0.25–5 (60) A |
The DIN-rail meters DAC 2100 (single-phase) and DAC 4300 (three-phase) have no letter-based type code. They are MID-approved (class B) and can also be used for billing subject to legal verification, e.g. for sub-metering.
The “i”: base meter or mME?
Only the EHZ541 has the “i” directly after the hyphen:
- EHZ541-i… = base meter with integrated LMN interface. It is connected directly to the smart meter gateway.
- EHZ541-… (without i) = modern metering device (mME) with an optical MSB interface on the back. It is connected to the gateway via an optical communication head and the BAB-01 communication adapter. The most convenient is the OKK-485, because like the BAB-01 it has an RJ12 plug; the OKK-232 also works, but has an RJ10 plug and needs an adapter.
DTZ541 and DDZ285 are always mME and are also connected via the BAB-01.
Energy direction: B, L, Z, S
| Letter | Meaning | Registers |
|---|---|---|
| B | import meter with backstop | 1.8.x (+A) |
| L | export meter with backstop | 2.8.x (−A) |
| Z | bidirectional meter – import and export registered separately, e.g. for homes with PV | 1.8.x and 2.8.x |
| S | export meter, net metering, without backstop | 2.8.0 |
All four are available for EHZ541, EHZ541-i, DTZ541 and DDZ285. The energy direction is fixed at the factory and cannot be changed in operation.
Tariff: E or D
- E = single tariff (register 1.8.0 or 2.8.0)
- D = dual tariff, e.g. peak and off-peak (additionally 1.8.1 and 1.8.2)
Dual tariff works in two steps:
- Ex works, the meter counts in single tariff.
- As soon as a tariff control signal is present, dual tariff is activated. From then on the meter counts in T1 or T2 depending on the signal.
On the DTZ541 and DDZ285 the signal comes via tariff terminals 13 and 15 or as a command from the gateway via the BAB-01 (the command has priority); on the EHZ541-i base meter it comes via the LMN interface.
Interface: optical, RJ12, RS485 or RS232
| Series | Letter | Meaning | Way to the gateway |
|---|---|---|---|
| EHZ541-i | no letter | optical LMN interface | optical communication head OKK-485 |
| EHZ541-i | C | LMN interface as RJ12 socket | directly with the LMN bus cable |
| EHZ541 | no letter | optical MSB interface | OKK-485 + BAB-01 (or OKK-232 + BAB-01) |
| DTZ541, DDZ285 | B (4th position) | MSB interface RS485 via terminals 27/28 | BAB-01 in the transparent terminal cover |
| DTZ541, DDZ285 | C (4th position) | MSB interface RS232 | BAB-01 |
B and C only differ in the cable path between meter and BAB-01. Towards the gateway, the BAB-01 always speaks LMN according to BSI TR-03109 via RJ12 at 921,600 bit/s – just like the LMN interface of the EHZ541-i.
Last position: class and radio
| Letter | Meaning | Available for |
|---|---|---|
| A | accuracy class A according to MID (EN 50470-3) | DTZ541, DDZ285 |
| B | accuracy class B according to MID (more accurate than A) | DTZ541 |
| L | additional LoRaWAN radio interface (on request) | EHZ541, DTZ541; approved for the EHZ541-i but not yet a series product |
EHZ541 and EHZ541-i carry no class letter – they are always MID class A. On the DTZ541 the L replaces the class letter. The DDZ285 is only available in class A.
LoRaWAN variants suit customers with their own LoRaWAN network: meter readings are read wirelessly and directly, without a smart meter gateway.
Examples: types “read aloud”
| Type | Meaning | Reading / to the gateway with |
|---|---|---|
| EHZ541-ZD | plug-in, mME, bidirectional, dual tariff | OKK-485 + BAB-01 |
| EHZ541-ZDL | as EHZ541-ZD, additionally LoRaWAN | LoRaWAN network or OKK-485 + BAB-01 |
| EHZ541-iZEC | plug-in, base meter, bidirectional, single tariff, LMN as RJ12 socket | LMN bus cable directly |
| EHZ541-iZD | plug-in, base meter, bidirectional, dual tariff, optical LMN | OKK-485 |
| DTZ541-ZDBA | screw-mounted, three-phase, bidirectional, dual tariff, RS485, class A | BAB-01 in the terminal cover |
| DTZ541-ZDCA | as DTZ541-ZDBA, but RS232 | BAB-01 |
| DTZ541-ZDCL | screw-mounted, three-phase, bidirectional, dual tariff, RS232, LoRaWAN | customer’s LoRaWAN network (wireless) |
| DDZ285-ZDBA | screw-mounted, single-phase, bidirectional, dual tariff, RS485, class A | BAB-01 in the terminal cover |
Not part of the type code: the current rating of the DTZ541 (60 A or 100 A) and special parameter settings – please state both when ordering. The product finder shows which combination suits your meter board.
Terminal cover with BAB-01
For DTZ541 and DDZ285 we supply the BAB-01 communication adapter as a set: firmly glued into a transparent terminal cover, with the rating plate laser-marked on the cover. The adapter is connected to the meter’s MSB interface (RS485 via terminals 27 and 28, or RS232); two RJ12 sockets lead to the gateway (LMN bus). The terminal cover is secured with a wire seal – plug in only the LMN bus cable before sealing. For the plug-in EHZ541, the BAB-01 is a single device and is connected via the optical head. Installation by qualified electricians only.
Rating plate: M marking and verification period
Next to the CE mark, the rating plate carries the metrology marking, e.g. M26: “M” and the year of marking (26 = 2026). The verification period (Eichfrist) under German law depends on it:
- 8 years for electronic electricity meters – including the DAC 2100 and DAC 4300.
- It is counted from the year of the M marking, not from delivery or installation.
- It runs until the end of the year: marking M26 → valid until the end of 2034.
Questions about a particular variant? Write to us at info@diinno.de – or ask our AI assistant at the bottom right.
Frequently asked questions
What does the “i” in EHZ541-i mean?
The “i” stands for the integrated LMN interface: the EHZ541-i is a base meter and is connected directly to the smart meter gateway. Without the “i”, the EHZ541 is a modern metering device (mME) that is connected to the gateway via an optical communication head and the BAB-01 communication adapter.
What does “ZD” in the type mean, e.g. EHZ541-ZD?
Z stands for bidirectional meter (import and export registered separately, needed e.g. with PV systems), D for dual tariff. EHZ541-ZD is therefore a plug-in three-phase meter (mME) for two energy directions with dual tariff.
What is the difference between DTZ541-ZDBA and DTZ541-ZDCA?
Only the fourth position, the MSB interface to the communication adapter: B = RS485 via terminals 27/28, C = RS232. Both variants can be connected to a smart meter gateway via the BAB-01; the only difference is the cable path between meter and adapter.
How long is the verification period of the meters?
For electronic electricity meters, the verification period (Eichfrist) is eight years. It is counted from the year of the metrology marking on the rating plate, not from installation: marking M26 (2026) → valid until the end of 2034.
Is the current rating 60 A or 100 A part of the type code?
No. The DTZ541 comes with both current ratings under the same type designation – please state the current rating when ordering. EHZ541 and DDZ285 are available with 60 A.